Pendent Sprinkler

QR 21.75QR 29.00

Country of origin:
Sold By: JerseyMEP

The TYCO Series TY-B, 5.6 K-factor, Pendent (TY325) Sprinklers are standard response, standard coverage, decorative 5 mm glass bulb type spray sprinklers designed for use in light, ordinary, or extra hazard, commercial occupancies such as banks, hotels, shopping malls, factories, refineries, and chemical plants.

 

View Product Datasheet       TY3251

QR 21.75QR 29.00

Clear

Specifications

upright pendent spDATASHEET – TY-B – TY315 – Upright Sprinkler

 

Specifications

Discharge Coefficient K = 5.6 GPM/psi½ (80,6 LPM/bar½)
Maximum Working Pressure 17.2 bar
Temperature Rating 68 Deg C, 79 Deg C
NPT 1/2 inches (male threaded)
Approvals UL, FM
Bulb Liquid Color Red, Yellow
Response Standard Response
Frame Bronze
Sprinkler Type Pendent

 